Normal running mode
|
On the H7 control box the heat pump is
switched on and automatic boiler boost is switched to:
- BOOST HOT WATER ONLY - only function 1 below applies.
- BOOST CENTRAL HEATING & HOT WATER - functions 1 to 3 apply.
When fitted, heat leak radiator has circuit at all
times
When the boost is used, the flow from a heat
pump is passed through into the return of the automatic boiler to be
boosted to a higher temperature.
Function 1.
Hot water mode on and cylinder thermostat is
calling,
Heating mode off, or room thermostat is satisfied
Heat pump and automatic boiler are running, charging the hot water
cylinder.
|
|
Status.
| Motorized Valve no 8 - Naturally Open to
the automatic boiler. (closed to the heat pump) |
| Motorized Valve no 10/17 - Naturally Open
to the hot water cylinder. (closed to the radiators) |
| Motorized Valve no 22 - Naturally Open to
the heat pump. |
|
Red = Flow. Blue = Return. Orange =
Preheated Return. White = Not flowing.
|
Function 2.
Hot water mode on and cylinder thermostat is
calling,
Heating mode on and room thermostat is calling
As above in function 1, heat pump and automatic
boiler are running, but in hot water and heating
mode motorized Valve no 10/17 is motored to mid position and the heat is
diverted to both the hot water cylinder and the radiator/U.F.H. system.
|
|
Status.
| Motorized Valve no 8 - Naturally Open to
the heat pump. (closed to the automatic boiler) |
| Motorized Valve no 10/17 Motored to mid
position. open to the hot water cylinder & radiators/U.F.H. |
| Motorized Valve no 22 - Naturally Open to
the heat pump. |
|
Red = Flow. Blue = Return. Orange = Preheated
Return. White = Not flowing.
|
Function 3.
Hot water mode on and cylinder thermostat is
satisfied
Heating mode on and room thermostat is calling
Heat pump and automatic boiler are running, when the hot water cylinder reaches optimum
temperature (detected by the cylinder thermostat), motorized Valve no
10/17 is motored open to the radiators/U.F.H. and closed to the hot water
cylinder.
|
|
Status.
| Motorized Valve no 8 - Naturally Open to
the heat pump. (closed to the automatic boiler) |
| Motorized Valve no 10/17 Motored open to
the radiators/U.F.H. & closed to the hot water cylinder |
| Motorized Valve no 22 - Naturally Open to
the heat pump. |
|
Red = Flow. Blue = Return. Orange = Preheated
Return. White = Not flowing.
|